Thursday, December 15, 2011

When Should Filter Media Be Cleaned?

by Dave Anderson
Customer Service, Tonka Equipment Company


Tonka has been asked this question by plant operators: 
"Should I chemically clean my filter media?"

On the surface this sounds like something that should be beneficial, but it may not be right for your filter.  This is especially true if you have Greensand™ or Ironman Sand™ filter media.


Greensand™ and Ironman Sand™ are coated with an active, beneficial coating of manganese dioxide which, when charged, oxidizes manganese as water flows through the filter. Unfortunately, chemicals that are used
to clean media of other precipitated compounds (calcium and magnesium hardness deposits, for instance) will remove the beneficial active coating on the Greensand™ or Ironman Sand™. For this reason Tonka strongly recommends against chemically cleaning filters that have Greensand™ or Ironman Sand™.


If you have concerns about media cleaning or your media not performing, please call our customer service department at 1-800-530-1887, and we’ll help you assess your needs and evaluate your filter operation.

Thursday, November 10, 2011

Delivering High Rate Media and Low Backwash Waste

by Alan Schneider
Tonka Equipment Company



The Spanaway Water District, located near Tacoma, Washington, needed a solution to manganese problems at a 900 GPM well, and a filter design that would fit into their new treatment building layout. They also wanted to minimize the backwash waste set up for discharge into a small infiltration basin. The District had previous failures of off-the-shelf standardized skidmounted vertical pressure filter systems, so they contacted Tonka, looking for a fresh, more robust approach.

Saturday, October 15, 2011

Protecting Your Filter Media from Mudball Formation

by TJ Stroebl
Tonka Equipment Company




Marble size mudballs on the surface of a filter
Mudballs! 
The word sounds innocent enough, but mudballs indicate problems in your filter bed. These solids accumulate within a filter and agglomerate into a ball of solids combined with the filter media.  These masses block the passage of water, causing higher velocity filtration and uneven distribution.  Ultimately, they affect filter performance and effluent quality, while shortening filter run lengths—all signs of problems.

Friday, September 30, 2011

Tonka Adds Water Industry Expertise



Plymouth, Minnesota -- Tonka Equipment Company, a leader in the manufacture of customized water treatment systems, is pleased to announce the hiring of Kurt Johnson to the position of Manager, Customer Service and Field Production.
  
Although new to Tonka, Johnson is not new to the water treatment industry. His experience encompasses an extensive 35-year consulting engineering career in the water treatment industry with design and construction management experience. In his new role, Johnson will lead the in-house and field technicians in start-ups and troubleshooting solutions in the field.

Friday, August 19, 2011

A Revolutionary Green Ion Exchange Technology -Tonka Pur-IX™


It is now possible for designers to take advantage of the high efficiency of ion exchange without producing large volume wastewater by using the Tonka Pur-IX™ system.


This fully-automated system consists of twenty small, stationary ion exchange vessels. All are piped through a single multi-port valve. Each vessel is at a different stage of resin exhaustion, allowing complete exhaustion of the resin without disrupting treated water quality. This means less resin volume is required than a conventional system and less wastewater is produced. Six of the twenty vessels are in different stages of regeneration, which sends the regenerant solution through multiple vessels for maximum exchange and minimum brine consumption.


The heart of the Pur-IX™ system is the patented PuriTech multi-port valve*. The valve contains an inner disc that indexes periodically to redirect flow and move the individual vessels through treatment and exchange. The internal valve disc itself is the only moving part, which accommodates true counter-current ion exchange while eliminating complicated valve nests and indexing carousels.


The Tonka Pur-IX™ system is applicable to any ion exchange process including nitrate, hardness, and organic removal.